This document provides a step-by-step guide for installers to configure the Acuvim meter specifically for FCAS testing, as part of this project
1- The meter must have a firmware version >= 6.15
2- The module must have a firmware version >= 1.26
3- The time zone should be set to "Australia/Sydney (AEDT)"
4- 50ms fast log enabled
5- Ethernet 2 DHCP is set to be auto
6- Fast read Mode Enabled and Fast mode set to be 50 ms fast read
7- Before enabling high-speed logging via the web interface, updating the baud rate setting to 2 on the meter is necessary. All Web2 modules are automatically set to 115200 baud rate upon clicking HTTP enabled. However, it's important to power cycle the meter/web2 module afterward. The baud rate is determined solely by the 'HTTP enabled' setting.